Rolls LFP Reference Documents:
Visit the links above, or rollsbattery.com for the most recent version of published documents.
Certain configurations, installations, services, and operating tasks should only be performed by qualified personnel in consultation with local utilities and/or authorized dealers. Qualified personnel should have training, knowledge, and experience in:
- Installing electrical equipment
- Applying applicable installation codes
- Analyzing and reducing hazards involved in performing electrical work
- Installing and configuring batteries
No responsibility is assumed by Rolls Battery for any consequences arising out of the use of this material.
Read Rolls LFP ESS Battery Operating Manual and safety instructions before installing the battery. Read Voltronic Inverter manuals for guidance on product features, functions, parameters and how to use the product safely. |
Connecting your Rolls S48-100LFP ESS Battery to Voltronic inverters over CANBUS
ROLLS LFP DESKTOP CONFIGURATION
To enable communication with a Voltronic inverter, the protocol must be set using the Rolls LFP Desktop App, and the setup steps below.
Physical Setup
Steps to setup are:
- Ensure the S48-100LFP ESS BMS is activated by hitting the RESET button. The SOC and RUN lights will be on.
- Address the DIP switch on the S48-100LFP ESS unit(s)
- If only one connected, address to Position 1 (See Figure 1).
- Connect the included RJ45-DB9 cable to one of the RS485 ports on the front of the battery.
- Connect the DB9 cable end to the RS485 to USB Serial adapter.
- Ensure the USB Serial adapter appears in device manager and the proper COM port is reflected in the software, below.
- Connect Rolls battery terminals (+ and -) to Voltronic inverter/charger.
- Connect Directly to the BMS CAN port of the inverter/charger.
- Use the appropriate RJ45-RJ45 cable to properly connect the CAN-bus signals with Voltronic inverters.
- Ensure the breaker is set to the “ON” position.
- Launch Rolls LFP Desktop App on your PC to configure CAN-bus mode.
Within the computer software Rolls LFP Desktop, after connecting to the battery…
- Select the appropriate COM port on your computer.
- Select a baud rate of 19200
- Select “Pack 1” from the righthand menu in Rolls LFP Desktop. (Or other, if directly connecting to another battery at a different address.
- Double check that the DIP switch is properly addressed to match.
- Select “Connect” and wait for connection to be established (1-3 seconds).
- Configure the unit to communicate with Voltronic devices.
- Click CAN on the top ribbon.
- Double click “PN-GDLT” for Voltronic.
- Wait for the confirmation popup.
- Ensure that the “BMS Information” Section at the bottom of the screen has updated to reflect the Voltronic CAN-bus Protocol.
Voltronic CANBUS Connection
- Ensure the output of the S48-100LFP ESS is disconnected, by setting the breaker on the front of the device to “OFF”.
- Return the DIP switch to the proper address for CANBUS mode.
- Connect the positive and negative terminals of the battery to the inverter, following applicable instructions, current, and code requirements.
- Connect the CANBUS port of the inverter to the CANBUS port of the Rolls S48-100LFP ESS with HOST CANBUS address (DIP 0000)
- Voltronic inverter pinouts, like for the more modern GSDHW Series use the following pinout, which will require a custom cable to interact with the Rolls BMS.
- Voltronic inverter pinouts, like for the more modern GSDHW Series use the following pinout, which will require a custom cable to interact with the Rolls BMS.
Rolls Pin | Rolls Battery | Voltronic Pin | Voltronic Inverter | (Port) |
1,2,7,8 | NC | 1,2,3,4,5 | RS485, RS232, NC | |
4,5 | Can-H, Can-L | 6 (H), 7 (L) | Can-H, Can-L | |
3,6 | Ground | 8 | Ground |
- Power-on the inverter by setting the breaker on the S48-100LFP ESS to “ON” and hitting the “RESET” button on the front of the unit.
Voltronic Device Setup and Debugging
- On the Voltronic device, go to System Settings, by long-pressing the up ↑ and down ↓ arrows simultaneously.
- Once inside the settings, you can use the up ↑ and down ↓ arrows to scroll through the settings, and hit enter to adjust the item.
- Refer to the Voltronic manual for additional settings options, like 03; output voltage, 01, output source priority, etc.
- Once inside the settings, you can use the up ↑ and down ↓ arrows to scroll through the settings, and hit enter to adjust the item.
- Set item 05 to BLU, to prioritize battery charging, or LBU to proritize load servicing, hit enter to save.
- Set item 11 to the maximum charging current for your setup (based on aprallel batteries), press enter to save.
- Set item 14 to PYL, or Lic, hit enter to save.
- If your inverter does not have these options, select USE, and set the charge and discharge voltages manually:
- Set 17 (bulk charge voltage) to 57.6
- Set 18 (float charge voltage) to 54-56
- Set 19 (Low DC cut off battery voltage) to >40
- Set 20 (Battery low voltage when on grid) based on your preference (40-50)
- Set 21 (Battery high voltage when on grid) to 54-57.6, per your preference
Note; off grid users may consider enabling a lower shutdown SOC to prioritize uptime over longevity.
BATTERY OPERATING LIMITS
Maximum Battery Operating Limits
The battery should not be operated outside these operating limits. The BMS will open its internal switch and disconnect the battery if any of these limits are exceeded.
Maximum Operating Limits | S48-100LFP ESS |
Continuous Discharge Current* | 63 Adc |
Continuous Charge Current* | 50 Adc |
Peak Current (300 milliseconds) | 500 Adc |
Operating Voltage (Min / Max) | 41.6 V / 58.4 V |
Charge Temperature (Min / Max) | 0°C / 55°C (32°F / 131°F) |
Discharge Temperature (Min / Max) | -20°C / 60°C (-4°F / 140°F) |
Storage Temperature (Min / Max) | -5°C / 45°C (23°F / 113°F) |
*Effects of AC Ripple must be taken into consideration when sizing/configuring a system |
Note: Intentional bypassing of a BMS to operate a battery outside its maximum and minimum limits voids warranty and may lead to safety concerns.
Minimum Battery Capacity
Using large solar arrays with battery banks that are too small can exceed the operating limits of the battery, potentially triggering over-current protection in the Battery Management System (BMS). Battery capacity must be sized to accommodate the maximum charge current of the system, or the charging devices must be adjusted to charge below the operating limit of the installed batteries. This value is determined by summing the charge capacities of all inverter/chargers and solar charge controllers in the system. Additionally, the battery peak capacity must be sized to support the surge requirements demanded by the load connected to the inverter. Ensure that the sum of all inverters peak power values matches the sum of all battery peak current values.